Addressing the AD-300 Lock
The AD-300 lock is addressed using the Schlage Utility Software (SUS), which is run from the Pideon PDA. The
address used by the AD-300 locks go from 0 to 15. lite blue uses an address list of 1 through 8. When
addressing an AD-300 lock it is important to remember this. An address of 0 for the AD-300 lock equals an
address of 1 in lite blue.
Example: The AD-300 lock is directly connected to the lite blue controller at RS485-1 then the address of the
AD-300 lock should be set to 1. If the AD-300 is connected to RS485-1 but daisy chained to another compatible
RS-485 device, then the address should be set to 2. A total of 8 devices may be connected.
After the AD-300 has been connected to the lite blue controller, make a note of the channel and address. This
information will be required to set up the lock in the software.
For additional information on the Schlage Utility Software see the Schlage Utility Software User's Guide.
To address the AD-300 lock:
1 Click Start on the PDA. A Menu will open with a list of programs.
2 Select the Schlage Utility Software option to open SUS.
3 Select Manager from the Log on as drop down menu.
4 Enter the password into the Password field. Default password is 123456
5 Click the Login button. The SUS program will open. The bottom of the screen will say No Device
Connected.
6 Connect the PDA to the AD-300 lock using the supplied USB cable.
7 Press the Schlage button twice on the AD-300 keypad. The bottom of the PDA screen will now display
AD300.
8 Click on the Options button at the bottom of the PDA screen. A list of options will open.