EasyManua.ls Logo

YASKAWA SGD7S

YASKAWA SGD7S
621 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.6 Convenient Function to Use during Trial Operation
7.6.3 Test without a Motor
7-27
7
Trial Operation and Actual Operation
5.
Click the Forward Button or the Reverse Button.
An origin search will be performed only while you hold down the mouse button. The motor will stop
when the origin search has been completed.
This concludes the origin search procedure.
7.6.3
Test without a Motor
A test without a motor is used to check the operation of the host controller and peripheral
devices by simulating the operation of the Servomotor in the SERVOPACK, i.e., without actually
operating a Servomotor. This test allows you to check wiring, debug the system, and verify
parameters to shorten the time required for setup work and to prevent damage to the machine
that may result from possible malfunctions. The operation of the motor can be checked with
this test regardless of whether the motor is actually connected or not.
Use Pn00C = n.X to enable or disable the test without a motor.
Parameter Meaning When Enabled Classification
Pn00C
n.0
(default setting)
Disable tests without a motor.
After restart Setup
n.1 Enable tests without a motor.
While the test without a motor is being executed, the display on the Panel Operate will
alternate between tSt and the status of the SERVOPACK.
Refer to the following section for information SERVOPACK status displays.
13.1.3 Status Displays on page 13-4
An asterisk is displayed on the status display of the Digital Operator while a test without a
motor is being executed.
Host controller
Reference
SERVOPACK
Reference
Response
Simulates operation
without a motor.
Response
Information

Table of Contents