8.7 Autotuning with a Host Reference
8.7.3 Applicable Tools
8-36
When the rigidity of the machine is low and vibration occurs when positioning is performed
When the position integration function is used
When proportional control is used
When mode switching is used
When the positioning completed width (Pn522) is too narrow
Refer to the following sections for details on custom tuning.
8.8 Custom Tuning on page 8-42
Preparations
Always check the following before you execute autotuning with a host reference.
The servo must be in ready status.
There must be no overtravel.
The servo must be OFF.
Position control must be selected if power is supplied to the motor (i.e., when the servo is ON).
The gain selection switch must be set to manual gain selection (Pn139 = n.0).
The first gains must be selected.
The test without a motor function must be disabled (Pn00C = n.0).
There must be no warnings.
The tuning-less function must be disabled (Pn170 = n.0).
The parameters must not be write prohibited.
8.7.3
Applicable Tools
The following table lists the tools that you can use to perform autotuning with a host reference
and the applicable tool functions.
8.7.4
Operating Procedure
Use the following procedure to perform autotuning with a host reference.
1.
Confirm that the moment of inertia ratio (Pn103) is set correctly.
2.
Click the Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
3.
Select Tuning in the Menu Dialog Box.
The Tuning Dialog Box will be displayed.
Click the Cancel Button to cancel tuning.
Tool Function Operating Procedure Reference
Panel Operator
You cannot perform autotuning with a host
reference from the Panel Operator.
Digital Operator Fn202
Σ-7-Series Digital Operator Operating Man-
ual (Manual No.: SIEP S800001 33)
SigmaWin+ Tuning - Tuning
8.7.4 Operating Procedure on page 8-36
CAUTION
If you are using an MP3000-Series Controller for phase control, set the mode selection to 1.
If 2 or 3 is selected for the mode, correct phase control may not be possible.