13.4 Utility Function (Fn) Operations on the Panel Operator
13.4.5 Initialize Parameters (Fn005)
13-16
13.4.5
Initialize Parameters (Fn005)
Refer to the following section for information on this utility function other than the procedure.
5.1.5 Initializing Parameter Settings on page 5-11
13.4.6
Clear Alarm History (Fn006)
Refer to the following section for information on this utility function other than the procedure.
12.2.5 Clearing the Alarm History on page 12-42
Step
Panel Display after
Operation
Keys Operation
1
Press the MODE/SET Key to enter Utility Function
Mode.
2 Press the UP Key or DOWN Key to display Fn005.
3
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown at the left will appear.
4
Press the MODE/SET Key to initialize the parameters.
When the initialization has been completed, donE will
flash on the display, and then the display shown on the
left will appear again.
5
To enable the change to the setting, turn the power supply to the SERVOPACK OFF and ON again
after the initialization of the parameter settings has been completed.
MODE
/
SET
DATA
/
MODE
/
SET
DATA
/
MODE
/
SET
DATA
/
MODE
/
SET
DATA
/
Step
Panel Display after
Operation
Keys Operation
1
Press the MODE/SET Key to enter Utility Function
Mode.
2 Press the UP Key or DOWN Key to display Fn006.
3
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown at the left will appear.
4
Press the MODE/SET Key to clear the alarm history.
When deleting the alarms has been completed, donE
will flash on the display, and then the display shown on
the left will appear again.
5
Press the DATA/SHIFT Key for approximately one sec-
ond to return the display to Fn006.