320 Fault tracing
2212 DATE WRONG
08.09 Alarm word5 b11
08.21 Pump alarm word b12
Date has not been set. Set the date and time (page 37).
2215 BOOSTING
08.09 Alarm word5 b14
08.21 Pump alarm word b15
Sleep boost is active. Informative alarm.
2216 PIPE FILLING
08.09 Alarm word5 b15
08.21 Pump alarm word b16
The soft pipefill function is
being performed.
Informative alarm.
2217 NO MORE PUMPS
08.10 Alarm word6 b0
08.21 Pump alarm word b17
No further pumps are
available for starting.
Check that all appropriate pumps are
switched on.
2218 CLEANING
08.10 Alarm word6 b1
08.21 Pump alarm word b8
A pump cleaning sequence
is in progress.
Informative alarm.
2219 AUTOCHANGE
08.10 Alarm word6 b2
08.21 Pump alarm word b18
The Autochange function is
being performed.
Informative alarm.
2220 SLEEPING
08.10 Alarm word6 b3
08.21 Pump alarm word b19
The drive has entered sleep
mode.
Informative alarm.
2221 START DELAY
08.10 Alarm word6 b4
08.21 Pump alarm word b20
A pump will start after the
start delay has elapsed.
Informative alarm.
2222 LC TANK FULL
08.10 Alarm word6 b5
08.21 Pump alarm word b23
The level of the liquid in the
container is very high (the
source selected by
parameter 79.15 High
switch is 1).
Informative alarm.
2223 LC TANK EMPTY
08.10 Alarm word6 b6
08.21 Pump alarm word b24
The level of the liquid in the
container is very low (the
source selected by
parameter 79.04 Low switch
is 1).
Informative alarm.
2224 MF MASTER LOST
08.10 Alarm word6 b7
08.21 Pump alarm word b21
The drive cannot detect a
master on the drive-to-drive
link, and is not itself allowed
to become master.
Check that there are drives on the drive-
to-drive link that are allowed to become
master.
Check the wiring of the drive-to-drive link.
2225 MF NO SHARED DATA
08.10 Alarm word6 b8
08.21 Pump alarm word b25
Shared signals not
received.
Check that at least one drive has signal
sharing enabled (parameter 76.12 Set as
source).
Check the status, communication
settings and wiring of the drive that is
sharing its signals.
2400 SOLUTION ALARM
(0x6F80)
08.08 Alarm word4 b1
Alarm generated by custom
application program.
Check custom application program.
Code
Alarm (fieldbus code),
other information
Cause What to do