EasyManua.ls Logo

ABB ACS580-07 - Changing Internal Overtemperature Supervision from DI6 to Another Digital Input; Switches; PNP Configuration for Digital Inputs (X2 & X3)

ABB ACS580-07
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal +24 V power supply External +24 V power supply
NPN connection (sink)
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
NPN connection (sink)
10 +24V
11 DGND
12 DCOM
13
DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
0VDC
+24 V DC
X4
X4
Changing internal overtemperature supervision from DI6 to another digital input
With option +E205 in frames R10 and R11, by default, digital input DI6 is used for the internal
overtemperature supervision of the drive cabinet. If it is required to use DI6 for an other
purpose, change the overtemperature supervision wiring from DI6 to another free digital
input either on the control unit or on the CMOD-01 multifunction extension module. Activate
the overtemperature supervision in the new digital input with these parameter settings:
1. Select the correct digital input from parameter 31.01 External event 1 source.
2. Check that parameter 31.02 External event 1 type is set to Fault = 0.
For more information, see the firmware manual.
WARNING!
Always connect the internal overtemperature supervision of the drive cabinet to a
free digital input or to CMOD-01 multifunction extension module if disconnected
from digital input DI6. Activate the change. Disconnection of overtemperature
supervision leads to overtemperature and can damage the drive.
Switches
PositionDescriptionSwitch
Bus not terminated (default)
TERM
ON
EFB link termination. Must be set
to the terminated (ON) position
when the drive (or another device)
is the first or last unit on the link.
TERM
Bus terminated
TERM
ON
Bias off (default)
BIAS
ON
Switches on the biasing voltages
to the bus. One (and only one)
device, preferably at the end of the
bus must have the bias on.
BIAS
Bias on
BIAS
ON
PNP configuration for digital inputs (X2 & X3)
Internal and external +24 V power supply connections for PNP configuration are shown in
the figure below.
120 Control unit

Table of Contents

Other manuals for ABB ACS580-07

Related product manuals