3. Check the air inlet and outlet meshes/filters of the cabinet. Clean when necessary.
For IP42 (UL Type 1 Filtered) drives: see section Cleaning the air inlet (door) meshes
(IP42 / UL Type 1 Filtered) below.
For IP54 (UL Type 12) drives: see section Cleaning the air inlet (door) meshes (IP42 /
UL Type 1 Filtered).
Cleaning the air inlet (door) meshes (IP42 / UL Type 1
Filtered)
WARNING!
Use a vacuum cleaner with an antistatic hose and nozzle. Using a normal vacuum
cleaner creates static discharges which can damage circuit boards.
Check the dustiness of the air inlet meshes. If the dust cannot be removed by vacuum
cleaning from outside through the grating holes with a small nozzle, proceed as follows:
1.
Stop the drive and do the steps in section Electrical safety precautions (page 20) before
you start the work.
2. Remove the fasteners at the top of the grating.
3. Lift the grating and pull it away from the door.
4. Vacuum clean the mesh.
5. Reinstall the mesh and grating in reverse order.
Replacing the air filters (IP54 / UL Type 12)
Check the air filters and replace if necessary (see Materials (page 214) for the correct filter
types).
Inlet (door) filters (IP54 / UL Type 12)
1.
Stop the drive and do the steps in section Electrical safety precautions (page 20) before
you start the work.
2. Remove the fasteners at the top of the grating.
3. Lift the grating and pull it away from the door.
4. Remove the air filter mat.
5. Place the new filter mat in the grating the metal wire side facing the door.
6. Reinstall the grating in reverse order.
Maintenance 137