NEC RATINGS
Output ratingsApp.
power
Max. cur-
rent
Input rat-
ing
Frame
size
Drive type
ACS580-07-
Heavy-overload useLight-overload use
P
Hd
I
Hd
P
Ld
I
Ld
S
N
I
max
I
1
hpAhpAkVAAA
150180200240170350240R80240A-4
150240*200260203418260R80260A-4
250302300361251542361R90361A-4
300361**350414298542414R90414A-4
■ Definitions
Nominal voltage of the drive. For the input voltage range, see section Electrical power network specific-
ation (page 211).
U
N
Nominal rms input current
I
1
Nominal output current (available continuously with no over-loading)
I
2
Apparent power (no overload)
S
Typical motor power in no-overload use
P
N
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes.
I
Ld
Typical motor power in light-overload use
P
Ld
Maximum output current. Available for two seconds at start, then as long as allowed by drive temperature.
I
max
Continuous rms output current allowing 50% overload for 1 minute every 10 minutes.
I
Hd
* Continuous rms output current allowing 30% overload for 1 minute every 10 minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 10 minutes.
Typical motor power in heavy-duty use
P
Hd
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F).
Note 2: To achieve the rated motor power given in the table, the rated current of the drive
must be higher than or equal to the rated motor current.
The DriveSize dimensioning tool available from ABB is recommended for selecting the drive,
motor and gear combination.
Output derating
■ Ambient temperature derating
Drive types other than ACS580-0414A-4 and ACS580-0430A-4
In the temperature range +40…50 °C (+104…122 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying
the current given in the rating table by the derating factor (k):
Technical data 173