NEC typeFuse (one fuse per phase)Input
current
A
Drive type
ACS580-07-
UL
class
TypeManufacturerVA
TJJS-600Bussmann6006004830505A-4
LA4BY800Ferraz6008005730585A-4
LA4BY800Ferraz6008006230650A-4
LA4BY800Ferraz6008007050725A-4
LA4BY900Ferraz6009008070820A-4
LA4BY1000Ferraz60010008070880A-4
Note 1: See also Implementing the emergency stop function (page 82).
Note 2: Fuses with higher current rating than the recommended ones must not be used.
Fuses with lower current rating can be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.
Dimensions and weights
WeightDepthWidthHeightDrive type
ACS580-07-
lbkgin.mmin.mmin.mm
46321026.5067316.9343084.432145R6
48522026.5067316.9343084.432145R7
56225526.5067320.8753084.432145R8
60627526.5067320.8753084.432145R9
90441027.4869832.6883084.432145R10 IP21/IP42
90441027.4869832.6883091.142315R10 IP54
97044027.4869832.6883084.432145R11 IP21/IP42
97044027.4869832.6883091.142315R11 IP54
Free space requirements
Free space requirements for cooling are given below.
Above *SideFront
in.mmin.mmin.mm
15.75400--5.91150
* measured from the base plate of the cabinet top.
> 400 mm (15.75ā€)
Technical data 179