Mechanical installation
Contents of this chapter
This chapter describes the mechanical installation procedure of the drive.
Examining the installation site
Examine the installation site:
• The installation site is sufficiently ventilated or cooled to remove heat from the drive.
See the technical data.
• The ambient conditions of the drive meet the specifications. See the technical data.
• There is enough free space above the drive to enable cooling, maintenance, and
operation of the pressure relief (if present).
• The floor that the drive cabinet is installed on is of non-flammable material, as smooth
as possible, and strong enough to support the weight of the unit. Check the floor flatness
with a spirit level. The maximum allowed deviation from the surface level is 5 mm in
every 3 meters. Level the installation site, if necessary, as the cabinet is not equipped
with adjustable feet.