Mechanical installation
Contents of this chapter
This chapter describes the mechanical installation procedure of the drive.
Examining the installation site
Examine the installation site:
The installation site is sufficiently ventilated or cooled to remove heat from the drive.
See the technical data.
The ambient conditions of the drive meet the specifications. See the technical data.
There is enough free space above the drive to enable cooling, maintenance, and
operation of the pressure relief (if present).
The floor that the drive cabinet is installed on is of non-flammable material, as smooth
as possible, and strong enough to support the weight of the unit. Check the floor flatness
with a spirit level. The maximum allowed deviation from the surface level is 5 mm in
every 3 meters. Level the installation site, if necessary, as the cabinet is not equipped
with adjustable feet.
4
Mechanical installation 51