8 kHz4kHz2 kHz1.5 kHzFrame size
0.580.780.921.00R11
0.580.780.921.00R11
* current derating for -0414A-4 and -0430A-4 at 35 C
Note:
Changing the value of parameter 97.01 Switching frequency reference does not require
derating.
Fuses (IEC)
The standard drive is equipped with aR fuses listed below.
Ultrarapid (aR) fuses (one fuse per phase)Input cur-
rent
(A)
Drive type
ACS580-07-
SizeType
(Mersen)
Type
(Buss-
mann)
VA
2
s(A)
U
N
= 400 V
1J320375C170M3816D690310002501450145A-4
1J320375C170M3816D690310002501690169A-4
1N320379C170M3817D690520003152060206A-4
2H300065A170M5408690790004002460246A-4
2S1046930K170M54106901550005002930293A-4
3X300078C170M64106902100006303630363A-4
3Y300079C170M64116903000007004300430A-4
3W1046956F170M64126904650008005050505A-4
3X1046957F170M64136906700009005850585A-4
3Y1046958F170M641469094500010006500650A-4
3A1046960F170M6416690195000012507250725A-4
3A1046960F170M6416690195000012508200820A-4
3B1046961F170M6417690245000014008800880A-4
Note 1: See also Implementing the emergency stop function (page 82).
Note 2: Fuses with higher current rating than the recommended ones must not be used.
Fuses with lower current rating can be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.
176 Technical data