Electrical power network specification
ACS580-07-xxxxx-4 drives: 380…480 VAC 3-phase ±10%. This is indicated in the
type designation label as typical input voltage levels 3~400/480 V AC.
Voltage (U
1
)
TN (grounded) and IT (ungrounded) systemsNetwork type
Maximum allowable prospective short-circuit current is 65 kA when the input cable
is protected with gG type fuses (IEC 60269) having maximum operating time of
0.1 seconds and maximum current rating:
Short-circuit withstand
strength (IEC 61439-1)
• 400 A for frames R6 to R8
• 630 A for frame R9
• 1000 A for R10
• 1250 A for R11
The drive is suitable for use on a circuit capable of delivering not more than 100,000
rms symmetrical amperes at 480 V maximum when the input cable is protected
with UL class T or L fuses. For selection of fuses for branch circuit protection, see
section Fuses for branch circuit protection (page 178). Fast acting class T and L or
faster are recommended in the USA. Obey local regulations.
Short-circuit current
protection (UL 508C)
50/60 Hz. Variation ±5% of nominal frequency.Frequency (f
1
)
Max. ± 3% of nominal phase to phase input voltageImbalance
0.98 (at nominal load)Fundamental power
factor (cos phi
1
)
Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous motorsMotor types
0 to U
1
, 3-phase symmetrical. This is indicated in the type designation label as
typical output voltage level 3 ~ 0...U
1
. U
max
at the field weakening point.
Voltage (U
2
)
0…500 HzFrequency (f
2
)
For drives with du/dt filter: 500 Hz
See section Ratings (page 171).
Current
3 kHz (typically)Switching frequency
300 m (984 ft).Maximum recommended
motor cable length
Longer cables cause a motor voltage decrease which limits the available motor
power. The decrease depends on the motor cable length and characteristics. Note
that a sine filter (optional) at the drive output also causes a voltage decrease.
Contact ABB for more information.
Note:
With motor cables longer than 100 m (328 ft), the EMC Directive requirements
may not be fulfilled.
Control unit connection data
See chapter Control unit (page 115).
Efficiency
Approximately 98% at nominal power level