Free space for door opening:
R6, R7: 400 mm (15.75”) in)
R8, R9: 500 mm (19.68 in)
R10. R11: 800 mm (31.50 in)
Maximum allowed plinth height for the
extraction/installation ramp
The maximum plinth height for the extraction/installation ramp delivered with the drive is 50
mm (1.97 in).
Typical power cable sizes
The table below gives typical copper and aluminum cable types with concentric copper
shield for the drives with nominal current. For the cable sizes accepted by the drive cabinet
cable entries and connection terminals, see Terminal and entry data for the power
cables (page 182).
US
2)
IEC
1)
Frame
size
Drive type ACS580-07-
Cu cable typeAl cable typeCu cable type
AWG/kcmil per phasemm
2
mm
2
U
N
= 400 V
3/03×1203×95R60145A-4
250 MCM3×1503×120R70169A-4
300 MCM3×2403×150R70206A-4
2×2/02×(3×95)2×(3×70)R80246A-4
2×3/02×(3×120)2×(3×95)R80293A-4
2×250 MCM2×(3×185)2×(3×120)R90363A-4
2×300 MCM2×(3×240)2×(3×150)R90430A-4
2×500 MCM or 3×250
MCM
3x(3x150)3x(3x95)R100505A-4
3x300 MCM4×(3x150)3x(3x120)R100585A-4
3x300 MCM4×(3x150)3x(3x150)R100650A-4
3×500 MCM or 4×300
MCM
4x(3x185)3x(3x185)R110725A-4
3×600 MCM or 4×400
MCM
4x(3x240)3x(3x240)R110820A-4
3×600 MCM or 4×400
MCM
4x(3x240)3x(3x240)R110880A-4
U
N
= 480 V
3/03x1203x95R60124A-4
180 Technical data