EasyManua.ls Logo

ABB ACS580-07 - Page 279

ABB ACS580-07
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Isolation areas:
DO1
CMOD-01
RO5
RO424 V
in
1
Reinforced insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
Relay outputs (50…52, 53…55):
Wire size max. 1.5 mm
2
Minimum contact rating: 12 V / 10 mA
Maximum contact rating: 250 V AC / 30 V DC / 2 A
Maximum breaking capacity: 1500 VA
Transistor output (42…44):
Wire size max. 1.5 mm
2
Type: Transistor output PNP
Maximum load: 4 kohm
Maximum switching voltage: 30 V DC
Maximum switching current: 100 mA / 30 V DC, short-circuit protected
Frequency: 10 Hz 16 kHz
Resolution: 1 Hz
Inaccuracy: 0.2%
External power supply (40…41):
Wire size max. 1.5 mm
2
24 V AC / V DC ±10% (GND, user potential)
Maximum power consumption: 25 W, 1.04 A at 24 V DC
Optional I/O extension modules 279

Table of Contents

Other manuals for ABB ACS580-07

Related product manuals