contactor feedback connector X250 with option +F250
cabinet door fan supply connector X8 and control X505
cabinet heater connector X300 with option +G300.
4. For drives without option +E205: Remove the shrouds (4a, 4b, 4c and 4d). To remove
the shroud on the power cable terminals, release the clips with a screwdriver and pull
the shroud out (4d). For drives with option +E205: Remove the shrouds 4a, 4b.
3
4a
4b
4c
4d
5. For drives without option +E205: Knock out holes in the shroud for the motor cable
conductors.
6. Peel off 3 to 5 cm of the outer insulation of the cables above the cable entries with the
conductive sleeves for the 360° high-frequency grounding.
5
7. Prepare the ends of the cables.
Electrical installation 97