Power supply
ValueMains
220/230 VAC, 1 phaseVoltage for OmniCore C30
100-230 VAC, 1 phase
i
+10%, -15%Voltage tolerance
+10%, -10%
i
50/60 HzFrequency
±3%Frequency tolerance
i
For IRB 14050 controller and CRB 15000 controller.
Note
The 2 phases (180-degree phase shift, with grounded neutral), also called
Single-phase three-wire system in North America, can be supported by this
controller.
Load current
There is no integrated fuse inside the OmniCore C30 controller. Add an external
fuse (time-delay) or circuit breaker (class K) according to full load current, as
marked on the controller nameplate. The following table shows the recommended
rating for an external fuse or circuit breaker.
Add an external circuit breaker (class K) according to full load current, as marked
on the controller nameplate. The following table shows the recommended rating
for an external fuse or circuit breaker.
DescriptionCurrent (A)Robot
10 A220/230 VAC, 1 phaseIRB 1100
10 A220/230 VAC, 1 phaseIRB 1200
10 A220/230 VAC, 1 phaseIRB 1300
10 A220/230 VAC, 1 phaseIRB 910INV
10 A220/230 VAC, 1 phaseIRB 920
10 A220/230 VAC, 1 phaseIRB 360
6 A100-230 VAC, 1 phaseIRB 14050
10 A220/230 VAC, 1 phaseCRB 1100
16 A in 100 VAC100-230 VAC, 1 phaseCRB 15000
6 A in 230 VAC
Residual current
An external earth fault protection (residual current device, RCD) is required based
on the following data:
Residual Current in controller (mA)Robot
< 30 mAIRB 1100
< 30 mAIRB 1200
Continues on next page
42 Product manual - OmniCore C30
3HAC060860-001 Revision: P