NoteAction
Make sure that the safety cable is connected
properly on both ends.
• If the connection seems OK, proceed
with step 5.
• If there is a problem with the connection,
proceed with step 11.
Check the safety cable connection:
X17.
10
Make sure that the safety cable is connected
properly on both ends.
• If the connection seems OK, the fault has
been fixed. Proceed with step 1.
• If there is a problem with the connection,
replace the safety related cables. See
12.
Restore the communication of the
safety cable between the modules
by reconnecting the cable X17.
11
• If the connection seems OK, the fault has
been fixed. Proceed with step 1.
• If the fault remains, see Troubleshooting
the power unit on page 383.
Replace the safety cable: X17.12
Product manual - OmniCore V250XT Type B 375
3HAC087112-001 Revision: A
© Copyright 2023-2023 ABB. All rights reserved.
7 Troubleshooting
7.3.3 Troubleshooting the drive unit
Continued