DescriptionName
Automatic Stop LED can be used to identify
the following status:
No color (not lit): Automatic Stop input
loop is open.
Green, solid: Automatic Stop input
loop is closed.
Automatic Stop LEDs (green)
AS1:Automatic Stop LED
channel 1
AS2:Automatic Stop LED
channel 2
AS1 & AS2
General Stop LED can be used to identify the
following status:
No color (not lit): General Stop input
loop is open.
Green, solid: General Stop input loop
is closed.
General Stop LEDs (green)
GS1:General Stop LED
channel 1
GS2:General Stop LED
channel 2
GS1 & GS2
Emergency stop output LED can be used to
identify the following status:
No color (not lit): Emergency stop
output is in State 0 (0V) status.
Green, solid: Emergency stop output
is in State 1 (24V) status.
Emergency stop output LEDs
(green)
ESO1:Emergency stop out-
put LED channel 1
ESO2:Emergency stop out-
put LED channel 2
ESO1 & ESO2
External emergency stop LED can be used
to identify the following status:
No color (not lit): External emergency
stop input loop is open.
Green, solid: External emergency stop
input loop is closed.
External emergency stop
LEDs (green)
ES1:External emergency
stop LED channel 1
ES2:External emergency
stop LED channel 2
ES1 & ES2
Troubleshooting procedure
NoteAction
Wait at least 1 min after power-on.Make sure the power has been off
for more than 10 seconds.
1
Power on the controller.
If LED TRK is green, proceed with 3.
If LED TRK is not green, proceed with
6.
Check LED TRK on Power distribu-
tion board, DSQC1085.
2
LED PC and LED HMI are green, pro-
ceed with 4.
LED PC and LED HMI are not green,
proceed with 13.
Check LEDs PC (Power distribution
board, DSQC1085) and HMI (Safety
board, DSQC1087).
3
If the STAT LED is:
Green, steady: Application is ready and
unit is operational. Proceed with step 5.
Green (uneven flashing ~1Hz): Installa-
tion Utility Application loaded and ready
for recovery operation. Proceed with
step 5.
Off or red flashing: The unit is faulty and
needs to be replaced. Proceed with step
13.
Check the STAT LED on the pro-
cessor board (DQSC1086).
4
If the PWR LED is:
Green, steady: Unit is operational. Pro-
ceed with step 9.
Green (pulsing ~1Hz): Communication
error to PS-side application. Proceed
with step 12.
Off or red: Proceed with step 13.
Check LED PWR on Processor
board, DSQC1086.
5
Continues on next page
Product manual - OmniCore V250XT Type B 419
3HAC087112-001 Revision: A
© Copyright 2023-2023 ABB. All rights reserved.
7 Troubleshooting