7352 Series Digital Multimeter Operation Manual
8.8 Notes Regarding Repair, Replacement, and Periodic Calibration
8-16
8.8 Notes Regarding Repair, Replacement, and Periodic Calibration
8.8.1 Before Asking for Repair
Before asking for repair, refer to and check Table 8-4.
Table 8-4    Before Asking for Repair
Problem Check item Solution
The power supply 
cannot be turned on.
Check the power cable. Change the power cable.
Check the power fuse. Replace the power fuse.
Key malfunction. Check whether the RMT indicator is on (in 
remote operation).
Press the LOCAL key to return to the local 
state.
Panel lock functions. Release the panel lock.
Voltage and resis-
tance cannot be 
measured.
Check that input cables are correctly connected 
between the VHz and COM A terminals, and 
between the V and COM B terminals.
Securely connect input cables between the 
VHz and COM A terminals, and 
between the V and COM B terminals.
Check whether the input cable is in good con-
dition and not broken.
Change the input cable.
Current cannot be 
measured.
Input terminals differ depending on the mea-
surement range.
Check that the input cable is correctly con-
nected to the current input terminals.
2000 nA and 2000 mA ranges: mA and COM 
A terminals
10 A range: A and COM B terminals
Securely connect the input cable to the 
correct terminals.
Check whether the protection fuse is service-
able and not open.
(For more information on how to check, refer 
to 8.1, “Replacing Fuses”.)
Replace the fuse.
For the A terminal, contact ADC CORPO-
RATION or a sales representative to repair 
this instrument.
Check whether the input cable is in good con-
dition and not broken.
Change the input cable.
For the high-resis-
tance measurement, 
the measurement 
value is not stable.
Induction noise is superimposed on the input 
cable.
Shield the DUT.
Use a shielded input cable.
Check that the power supply frequency setting 
is the same as the local commercial power sup-
ply frequency.
Perform the measurement with SLOW1 or 
SLOW2.
Sampling does not 
operate.
Check whether the HOLD indicator is on (in 
HOLD operation).
Press the TRIG or HOLD key and check 
whether sampling operates.
(During the remote operation, panel keys 
do not function. Therefore, after releasing 
the remote operation, press any panel key.)
A long trigger delay time is set. Check the trigger delay time.