EasyManua.ls Logo

Agilent Technologies 35670A

Agilent Technologies 35670A
796 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Limit Fail Register Set
The Limit Fail register set monitors limit test results for all traces. See figure 1-8.
Bits in the Limit Fail condition register are set to 1 under the following conditions:
Trace A Upper Failed (bit 0) is set to 1 when limit testing is enabled and any point on trace A
exceeds its upper limit.
Trace A Lower Failed (bit 1) is set to 1 when limit testing is enabled and any point on trace A falls
below its lower limit.
Trace B Upper Failed (bit 2) is set to 1 when limit testing is enabled and any point on trace B exceeds
its upper limit.
Trace B Lower Failed (bit 3) is set to 1 when limit testing is enabled and any point on trace B falls
below its lower limit.
Trace C Upper Failed (bit 4) is set to 1 when limit testing is enabled and any point on trace C exceeds
its upper limit.
Trace C Lower Failed (bit 5) is set to 1 when limit testing is enabled and any point on trace C falls
below its lower limit.
Trace D Upper Failed (bit 6) is set to 1 when limit testing is enabled and any point on trace D
exceeds its upper limit.
Trace D Lower Failed (bit 7) is set to 1 when limit testing is enabled and any point on trace D falls
below its lower limit.
Figure 1-8 also shows the commands you use to read and write the Limit Fail registers. See chapter 20
for more information about these commands.
The Agilent 35670A’s Status Registers
1-17
1-8. The Limit Fail Register Set

Table of Contents

Other manuals for Agilent Technologies 35670A

Related product manuals