11-11
PPC Manual Revision 1
11.1.6 Setting Bar-graph Display Function
Description
OUT, Output
Displayed by 10% increment of output
0% 100%
PV, SP, and Analog Input, TSP
Displayed by 10% increment of
analog input/PV input range
0% 100%
Deviation
Deviation negative side Deviation positive side
Deviation negative side and deviation positive side are displayed by 10% increment of deviation.
Indication is unlit when SP
–
(deviation display band (BDV)) ≤ PV ≤ SP + (deviation display band (BDV)).
Indication is unlit when TSP –
(deviation display band (BDV)) ≤ PV ≤ TSP + (deviation display band (BDV)).
Deviation is more than -60%.
0% 100%
Deviation is more than +60%.
Deviation negative side Deviation positive side
IN = TC Type K -270.0 to 1370.0ºC
BDV = 82
ºC (5%), SP = 500.0ºC, PV = 800.0ºC
All indications are unlit when the deviation is 418 ≤ PV ≤ 582ºC.
992.1ºC or more
910.1 to 992.0ºC
828.1 to 910.0ºC
746.1 to 828.0ºC
664.1 to 746.0ºC
582.1 to 664.0ºC
356.0 to 417.9ºC
254.0 to 355.9ºC
172.0 to 253.9ºC
90.0 to 171.9ºC
8.0 to 89.9ºC
to 7.9ºC
Chapter 11: Setting Display and Key Functions