Chapter 23: D Registers (Holding Registers)
Loop-1 PID Setting of Groups 1 to 8 and R (D3001 to D3500)
Register
No.
Description Range and meaning of value
D3001
P_L1_1
Proportional band of group 1
0.0 to 999.9%
When 0.0% is set, it operates as 0.1%.
D3002
I_L1_1
Integral time of group 1

1 to 6000 s
D3003
D_L1_1
Derivative time of group 1

1 to 6000 s
D3004
OH_L1_1
Control output high limit of group 1 
D3005
OL_L1_1
Control output low limit of group 1 
D3006
MR_L1_1
Manual reset of group 1
Enabled when integral time is OFF.
The manual reset value equals the output value
when PV = SP.
-5.0 to 105.0%
D3007
HYS_L1_1
 
D3009
HY.UP_L1_1
Upper-side hysteresis (in ON/OFF
of group 1

D3010
HY.LO_L1_1
Lower-side hysteresis (in ON/OFF
of group 1
D3011
DR_L1_1
Direct/reverse action switch of group 1
0: RVS: Reverse action
1: DIR: Direct action