23-30
PPC Manual Revision 1
Chapter 23: D Registers (Holding Registers)
Loop-1 Control Action-related Setting (D3501 to D3600)
Register
No.
Description Range and meaning of value
D3501
SC_L1
Super function
0: O
1: O
Enables to answer the wider characteristic
changes compared with response mode.
3:
Enables quick follow-up and short converging
time of PV for the changed SP.
4: Overshoot suppressing function (strong
N
ote: Setpoints 2 and 3 must be used in PID control
or PI control. Disabled in the following controls:
1
Do not use the function for the control
processes with responses similar to ow or
pressure control.
D3502
D3503
AT.TY_L1
Auto-tuning type
0: Normal
1: Stability
D3504
AT.OH_L1
Output high limit in auto-tuning
-5.0 to 105.0%
D3505
AT.OL_L1
Output low limit in auto-tuning
D3506
AT.BS_L1
SP bias in auto-tuning
D3507 to D3510
D3511
STM
Sample PI sampled time 0 to 9999 s
D3512
SWD
Sample PI control time span 0 to 9999 s
D3513
GW_L1
Non-linear control gap width
0: OFF
D3514
GG_L1
Non-linear control gain 0.001 to 1.000
D3515 to D3516
D3517
BD
Batch PID deviation setpoint 0
D3518
BB
Batch PID bias 0.0 to 100.0%
D3519
BL
Batch PID lock-up width 0
D3520
D3525
D3526
AR_L1
A
nti-reset windup (excess integration
0
: AUTO, 50.0 to 200.0%
D3527
OPR_L1
Output velocity limiter 0
D3528
OLMT_L1
Output limiter switch
0
D3529 to D3530
D3531
MPON_L1
Manual preset output number selection
Select the output used in MAN mode when
switched from AUTO to MAN mode.
0: OFF (Hold the control output in AUTO mode
1: U
2: U
3: U
4: U
5: U
D3532
MPO1_L1
Manual preset output 1
-5.0 to 105.0%
However, output is limited to the output high limit
and low limit.
D3533
MPO2_L1
Manual preset output 2
D3534
MPO3_L1
Manual preset output 3
D3535
MPO4_L1
Manual preset output 4
D3536
MPO5_L1
Manual preset output 5
D3537 to D3550