23-39
PPC Manual Revision 1
Chapter 23: D Registers (Holding Registers)
Loop-2 Alarm Function Setting (D3901 to D4000)
Register
No.
Description Range and meaning of value
D3901 AL1.T_L2 Alarm-1 type
A
L1.T_L2 to AL8.T_L2
00: Disable
01: PV high limit
02: PV low limit
03: SP high limit
04: SP low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
09: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
21: Analog input RSP high limit
22: Analog input RSP low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
A
L1.W_L2 to AL8.W_L2
0: Without Stand-by action
1: With Stand-by action
A
L1.D_L2 to AL8.D_L2
0: Alarm output: Energized
1: Alarm output: De-energized
A
L1.L_L2 to AL8.L_L2
0
: OFF
1: Latch 1
2: Latch 2
3: Latch 3
4: Latch 4
When the PPC5 parameter is set by key stroke,
the alarm type, stand-by action, energized/de-
energized, and latch comprise one parameter.
D3902 AL1.W_L2 Alarm-1 stand-by action
D3903 AL1.D_L2 Alarm-1 energized/de-energized
D3904 AL1.L_L2 Alarm-1 latch
D3905 AL2.T_L2 Alarm-2 type
D3906 AL2.W_L2 Alarm-2 stand-by action
D3907 AL2.D_L2 Alarm-2 energized/de-energized
D3908 AL2.L_L2 Alarm-2 latch
D3909 AL3.T_L2 Alarm-3 type
D3910 AL3.W_L2 Alarm-3 stand-by action
D3911 AL3.D_L2 Alarm-3 energized/de-energized
D3912 AL3.L_L2 Alarm-3 latch
D3913 AL4.T_L2 Alarm-4 type
D3914 AL4.W_L2 Alarm-4 stand-by action
D3915 AL4.D_L2 Alarm-4 energized/de-energized
D3916 AL4.L_L2 Alarm-4 latch
D3917 AL5.T_L2 Alarm-5 type
D3918 AL5.W_L2 Alarm-5 stand-by action
D3919 AL5.D_L2 Alarm-5 energized/de-energized
D3920 AL5.L_L2 Alarm-5 latch
D3921 AL6.T_L2 Alarm-6 type
D3922 AL6.W_L2 Alarm-6 stand-by action
D3923 AL6.D_L2 Alarm-6 energized/de-energized
D3924 AL6.L_L2 Alarm-6 latch
D3925 AL7.T_L2 Alarm-7 type
D3926 AL7.W_L2 Alarm-7 stand-by action
D3927 AL7.D_L2 Alarm-7 energized/de-energized
D3928 AL7.L_L2 Alarm-7 latch
D3929 AL8.T_L2 Alarm-8 type
D3930 AL8.W_L2 Alarm-8 stand-by action
D3931 AL8.D_L2 Alarm-8 energized/de-energized
D3932 AL8.L_L2 Alarm-8 latch
D3933
VT1_L2
PV velocity alarm time setpoint 1
D3934
VT2_L2
PV velocity alarm time setpoint 2
D3935
VT3_L2
PV velocity alarm time setpoint 3
D3936
VT4_L2
PV velocity alarm time setpoint 4
D3937
VT5_L2
PV velocity alarm time setpoint 5
D3938
VT6_L2
PV velocity alarm time setpoint 6
D3939
VT7_L2
PV velocity alarm time setpoint 7
D3940
VT8_L2
PV velocity alarm time setpoint 8