14-8
PPC Manual Revision 1
Errors during operation (Input/output Action)
Error
description
PV input, RSP input,
and aux. analog input
Control
computation
Control output
Retransmission
output
Alarm
action
Analog output
(control output,
retransmission
output)
Voltage
pulse
output
(control
output)
Relay
output
(control
output)
Contact
input
Contact
(alarm)
output
Communication
Burnout error when
RSP input is used for
control (Loop 1, Loop
2)
Depends on the setting
of the parameter BSL
of the analog terminal
connected to the RSP
where the error occurs.
Upscale: 105%
Downscale: -5%
Normal action
When in AUTO and
RUN modes: Error
preset output
When in MAN
mode: MAN output
Normal action
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal action
Chapter 14: Troubleshooting