17-24
PPC Manual Revision 1
Chapter 17: Software Setting Flow and Navigation
Description
Data which can be downloaded by one operation are a user file name, system data (only
control mode and control period) and parameter data.
Once a password has been set, it must be entered whenever you upload, download, or
compare. The password default value is non-setting. The password can be up to eight
single-byte alphanumeric characters and is case sensitive.
Individual data can be downloaded as follows.
Click on [Communication] – [Download Parameter Data] in the menu.
<Execute Communication window>
Serial Port: A port available for a PC is automatically displayed.
Stop Bit, Parity, Baud Rate, and address: Set these items according to the controller’
s communication conditions. Data length: xed 8 bit
IP Address: Set this address according to the controller’ s IP address (for Ethernet
communication).
Serial Address: Set the controller’ s RS-485 communication address if
communication is made via an Ethernet/RS-485 converter. (Not allowed to be
duplicated)
Port Number: Set the port number. (Decimal Number or Hexadecimal Number)
If data is downloaded via a maintenance port, nothing is displayed in the Alarm
Generation Status in the Execute Communication window.
Note
Do not disconnect a connection cable or turn off the
controller
power supply during a
download.