DECS-200 BESTCOMS Software 5-11
Figure 5-14. System Settings Screen, Startup Tab
OEL Type
Overexcitation Limiter Type tab settings are illustrated in Figure 5-15 and described in the following
paragraphs.
Figure 5-15. System Settings Screen, OEL Type Tab
OEL Limiter Style.
Selects either the summing-point type of overexcitation limiter or the takeover-type of
overexcitation limiter.
OEL Setting Selection Option.
Selects the on-line and off-line OEL settings for various 52J/K and 52L/M
contact statuses.