Modbus™ Communication DECS-200
7-18
Table 7-16. Information Category C6 (Setpoint Parameters)
Registers Data Description Access
Data
Format
47661-62
PF mode setpoint adjustable minimum, adjustable from 0.5 to 1.0 in
0.005 increments
RW R32_23
47663-64
FCR mode setpoint maximum (in % of rated field current), adjustable
from 100 to 120% in 0.1% increments
RW R32_23
47665-66
AVR mode setpoint maximum (in % of rated generator output
voltage), adjustable from 100 to 110% in 0.1% increments
RW R32_23
47667-68
Var mode setpoint maximum (in % of rated generator VA),
adjustable from -100 to 100% in 0.1% increments
RW R32_23
47669-70
PF mode setpoint adjustable maximum, adjustable from -1.0 to -0.5
in 0.005 increments
RW R32_23
47671-72
Minimum value for FCR mode setpoint adjustable minimum (in % of
rated field current) = 0%
R R32_23
47673-74
Minimum value for AVR mode setpoint adjustable minimum (in % of
rated generator output voltage) = 80%
R R32_23
47675-76
Minimum value for var mode setpoint adjustable minimum (in % of
rated generator VA) = -100%
R R32_23
47677-78
Minimum value for PF mode setpoint adjustable minimum R R32_23
47679-80
Maximum value for FCR mode setpoint adjustable maximum (in %
of rated field current) = 120%
R R32_23
47681-82
Maximum value for AVR mode setpoint adjustable maximum in (in %
of rated generator output voltage) = 110%
R R32_23
47683-84
Maximum value for var mode setpoint adjustable maximum (in % of
rated generator VA) = 100%
R R32_23
47685-86
Maximum value for PF mode setpoint adjustable maximum R R32_23
47687-88
Step size for FCR mode setpoint adjustable maximum (in % of rated
field current) = 0.1%
R R32_23
47689-90
Step size for AVR mode setpoint adjustable maximum (in % of rated
generator output voltage) = 0.1%
R R32_23
47691-92
Step size for var mode setpoint adjustable maximum in % of rated
generator VA) = 0.1%
R R32_23
47693-94
Step size for PF mode setpoint adjustable maximum = 0.005 R R32_23
47695
FCR preposition mode: 0 = maintained / 1 = release RW UI16
47696
AVR preposition mode: 0 = maintained / 1 = release RW UI16
47697
Var preposition mode: 0 = maintained / 1 = release RW UI16
47698
PF preposition mode: 0 = maintained / 1 = release RW UI16
47699-700
FCR minimum setpoint (in amps) = % of nominal x rated field
current:(regs. 47655-56) x (regs. 47529-30) / 100
R- R32_23
47701-02
AVR minimum setpoint (in volts) = % of nominal x rated gen.
voltage:(regs. 47657-58) x (regs. 47525-26) / 100
R- R32_23
47703-04
Var minimum setpoint (in kvar) = % of nominal x rated generator R- R32_23