EasyManua.ls Logo

BENSHAW RSi GM2 Series - Page 227

BENSHAW RSi GM2 Series
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
217
Table of Functions
890054-00-00
GM2 Series VFD
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
source
1
Keypad-2
2
V1
4
V0
5
I2
6
Int 485
8
FieldBus
Cn.54
2
0h1436
Positive
direction
+torque limit
0.0200.0 (%)
180
O
X
O
p.118
Cn.55
2
0h1437
Positive
direction
regeneration
(-) torque limit
0.0200.0 (%)
180
O
X
O
p.118
Cn.56
2
0h1438
Reverse
direction
regeneration
(-) torque limit
0.0200.0 (%)
180
O
X
O
p.118
Cn.57
2
0h1439
Reverse
direction
+torque limit
0.0200.0 (%)
180
O
X
O
p.118
Cn.70
0h 1446
Speed search
mode
selection
0
Flying Start-1
3
0
X
O
O
p.128
1
Flying Start-2
Flying
Start-1
Cn.71
0h1447
Speed search
operation
selection
bit
00001111
0000
[4]
X
O
O
p.128
1
Selects the speed
search function at
acceleration.
10
Initialization after a
fault
100
Restart after
instantaneous
power interruption
1000
Starting with
power-on
Cn.72
5
0h1448
Speed search
reference
current
80200 (%)
150
O
O
O
p.128
Cn.73
6
0h1449
Speed search
proportional
gain
09999
Flying
Start-1
O
O
O
p.128
: 100
Flying
Start-2
: 600
7
Cn.74
6
0h144A
Speed search
integral gain
09999
Flying
Start-1
O
O
O
p.128
: 200
Flying
Start-2
: 1000

Table of Contents

Related product manuals