Table of Functions
218
GM2 Series VFD
890054-00-00
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
Cn.75
6
0h144B
Output block
time before
speed search
0.060.0 (s)
1
X
O
O
p.128
Cn.77
0h144D
Energy
buffering
selection
0
No
0: No
X
O
O
p.124
1
KEB-1
2
KEB-2
Cn.78
8
0h144E
Energy
buffering start
level
110.0200.0 (%)
125
X
O
O
p.124
Cn.79
8
0h144F
Energy
buffering stop
level
Cn78210.0 (%)
130
X
O
O
p.124
Cn.80
8
0h1450
Energy
buffering P
gain
020000
1000
O
O
O
p.124
Cn.81
8
0h1451
Energy
buffering I
gain
120000
500
O
O
O
p.124
Cn.82
8
0h1452
Energy
buffering Slip
gain
02000.0%
30
O
O
O
p.124
Cn.83
8
0h1453
Energy
buffering
acceleration
time
0.0600.0 (s)
10
O
O
O
p.124
[1] Applicable to 5.5 - 7.5 kW products. Refer to 5.15 for information on all capacities.
[2] Displayed when dr.09 is set to 4 (IM Sensorless). This will change the initial value of the parameter at
Ad.74 (Torque limit) to 150%.
[3] Will not be displayed if dr.09 is set to 4 (IM Sensorless).
[4] It will be displayed on the keypad as
[5] Displayed when any of the Cn.71 code bits are set to 1 and Cn70 is set to 0 (Flying Start-1).
[6] Displayed when any of the Cn.71 code bits are set to 1.
[7] The initial value is 1200 when the motor-rated capacity is less than 7.5 kW
[8] Displayed when Cn.77 is not set to 0 (No).