Installing the Inverter
20
GM2 Series VFD
890054-00-00
Input Terminal Labels and Descriptions
Category
Terminal
Labels
Name
Description
Multi-
function
(digital)
terminal
configuration
P1P5
Multi-function
(digital) Input 1-5
Configurable multi-function (digital) input
terminals.
Factory defaults are setup as follows:
P1: Fx
P2: Rx
P3: BX
P4: RST
P5: Speed-L
CM
Sequence
common terminal
Common terminal for multi-function (digital)
terminals, RS-485 communication, and analog
inputs and outputs.
Analog input
VR
12V source
terminal for
frequency
reference setting
Source voltage for reference frequency via
analog voltage input.
Maximum Voltage Output: 12 V
Maximum Current Output: 100 mA
Potentiometer: 1/5 kΩ
V1
Frequency setting
(voltage) terminal
Voltage input for 0 - 10V reference frequency.
Unipolar: 010 V (12 V Max.)
Bipolar: -1010 V (±12 V Max.)

Table of Contents