CG Drives & Automation,01-5326-01r5 Functional Description 99
Motor Speed [225]
Set the nominal asynchronous motor speed.
Communication information
Motor Poles [226]
When the nominal speed of the motor is ≤500 rpm, the
additional menu for entering the number of poles, [226],
appears automatically. In this menu the actual pole number
can be set which will increase the control accuracy of the AC
drive.
Communication information
Motor Cos Ï• [227]
Set the nominal Motor cosphi (power factor).
Communication information
Motor ventilation [228]
Parameter for setting the type of motor ventilation. Affects
the characteristics of the I
2
t motor protection by lowering
the actual overload current at lower speeds.
Communication information
When the motor has no cooling fan, None is selected and
the current level is limited to 55% of rated motor current.
With a motor with a shaft mounted fan, Self is selected and
the current for overload is limited to 87% from 20% of
synchronous speed. At lower speed, the overload current
allowed will be smaller.
When the motor has an external cooling fan, Forced is
selected and the overload current allowed starts at 90% from
rated motor current at zero speed, up to nominal motor
current at 70% of synchronous speed.
Fig. 94 shows the characteristics with respect for Nominal
Current and Speed in relation to the motor ventilation type
selected.
225 Motor Speed
Default: (n
MOT
)
rpm (see Note 2 page 97)
Range: 30 - 18000 rpm
Resolution 1 rpm, 4 sign digits
WARNING!
Do NOT enter a synchronous (no-load)
motor speed.
NOTE: Maximum speed [343] is not automatically
changed when the motor speed is changed.
NOTE: Entering a wrong, too low value can cause a
dangerous situation for the driven application due to
high speeds.
Modbus Instance no/DeviceNet no: 43045
Profibus slot/index 168/204
EtherCAT and CANopen index (hex) 4be5
Profinet IO index 19429
Fieldbus format UInt. 1=1 rpm
Modbus format UInt
226 Motor Poles
Default: 4
Range: 2-144
Modbus Instance no/DeviceNet no: 43046
Profibus slot/index 168/205
EtherCAT and CANopen index (hex) 4be6
Profinet IO index 19430
Fieldbus format Long, 1=1 pole
Modbus format EInt
227 Motor Cosϕ
Default: Cosϕ
NOM
(see Note 2 page 97)
Range: 0.45 - 1.00
Modbus Instance no/DeviceNet no: 43047
Profibus slot/index 168/206
EtherCAT and CANopen index (hex) 4be7
Profinet IO index 19431
Fieldbus format Long, 1=0.01
Modbus format EInt
228 Motor Vent
Default: Self
None 0 Limited I
2
t overload curve.
Self 1
Normal I
2
t overload curve. Means that the
motor stands lower current at low speed.
Forced 2
Expanded I
2
t overload curve. Means that
the motor stands almost the whole current
also at lower speed.
Modbus Instance no/DeviceNet no: 43048
Profibus slot/index 168/207
EtherCAT and CANopen index (hex) 4be8
Profinet IO index 19432
Fieldbus format UInt
Modbus format UInt