EasyManuals Logo

ComAp InteliCompact NT Reference Guide

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
180
Setpoint: Overspeed Sd
Group
Engine Protect
Range [units]
100 … 150 [%]
Related
applications
All
Description
Threshold for overspeed protection. Relative to the nominal speed.
Setpoint: Batt Overvolt
Group
Engine Protect
Range [units]
Batt Undervolt ... 36 [V]
Related
applications
All
Description
Warning threshold for high battery voltage alarm.
Setpoint: Batt Undervolt
Group
Engine Protect
Range [units]
8 ... Batt Overvolt [V]
Related
applications
All
Description
Warning threshold for low battery voltage alarm.
Setpoint: Batt Volt Del
Group
Engine Protect
Range [units]
0 ... 600 [s]
Related
applications
All
Description
Delay for low battery voltage alarm.
Setpoint: AI1 Yel
Group
Engine Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 1.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals