InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
180
Setpoint: Overspeed Sd
Group
Engine Protect
Range [units]
100 150 [%]
Related
applications
All
Description
Threshold for overspeed protection. Relative to the nominal speed.
Setpoint: Batt Overvolt
Group
Engine Protect
Range [units]
Batt Undervolt ... 36 [V]
Related
applications
All
Description
Warning threshold for high battery voltage alarm.
Setpoint: Batt Undervolt
Group
Engine Protect
Range [units]
8 ... Batt Overvolt [V]
Related
applications
All
Description
Warning threshold for low battery voltage alarm.
Setpoint: Batt Volt Del
Group
Engine Protect
Range [units]
0 ... 600 [s]
Related
applications
All
Description
Delay for low battery voltage alarm.
Setpoint: AI1 Yel
Group
Engine Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 1.