InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
187
Setpoint: Gen Freq Del
Group
Gener Protect
Range [units]
0 ... 600.0 [s]
Related
applications
All
Description
Delay for generator underfrequency and overfrequency alarm.
Setpoint: BusMeasError
Group
Gener Protect
Range [units]
DISABLED, ENABLED [s]
Related
applications
MINT
Description
If the protection is ENABLED the Bus Measure error is detected in MINT
application when the voltage on controller’s bus terminals is out of limits 20
seconds after:
a) GCB (own) was closed in MAN or AUT mode.
b) MCB (feedback) was closed in AUT mode.
c) Any other GCB in power management group (on CAN bus)
was closed.
The alarm is activated after 20s. However, the GCB (own) closing is blocked
immediately for safety reasons.
Setpoint: Reverse Pwr BOC
Group
Gener Protect
Range [units]
1 ... 50 [%]
Related
applications
All
Description
Threshold for generator reverse power alarm, relative to the Nominal power.
Setpoint: Reverse Pwr Del
Group
Gener Protect
Range [units]
0 ... 600.0 [s]
Related
applications
All
Description
Delay for generator reverse power alarm.
Setpoint: ExcitationLoss
Group
Gener Protect
Range [units]
0 ... 150 [%]
Related
applications
All

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals