186
Setpoint: Gen V Del
Group
Gener Protect
Range [units]
0 ... 600.0 [s]
Related
applications
All
Description
Delay for generator undervoltage and overvoltage alarm.
Setpoint: Volt Unbal BOC
Group
Gener Protect
Range [units]
1 ... 200 [%]
Related
applications
All
Description
Threshold for generator voltage unbalance alarm, relative to the nominal
voltage (setpoint Nominal Volts).
Setpoint: Volt Unbal Del
Group
Gener Protect
Range [units]
0 ... 600.0 [s]
Related
applications
All
Description
Delay for generator voltage unbalance alarm.
Setpoint: Gen >Freq BOC
Group
Gener Protect
Range [units]
Gen <Freq BOC ... 200 [%]
Related
applications
All
Description
Threshold for generator overfrequency alarm, relative to the nominal
frequency (setpoint Nominal Freq).
Setpoint: Gen <Freq BOC
Group
Gener Protect
Range [units]
50 ... Gen >Freq BOC [%]
Related
applications
All
Description
Threshold for generator underfrequency alarm, relative to the nominal
frequency (setpoint Nominal Freq).

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals