InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
185
Setpoint: Amps Unbal Del
Group
Gener Protect
Range [units]
0 ... 600.0 [s]
Related
applications
All
Description
Delay for generator current unbalance alarm.
Setpoint: EarthFault Sd
Group
Gener Protect
Range [units]
1 ... 10000 [A]
Related
applications
All
Description
Limit value for Earth Fault Current protection.
Setpoint: EarthFault Del
Group
Gener Protect
Range [units]
0.1 ... 600.0 [s]
Related
applications
All
Description
Delay for Earth Fault Current protection.
Setpoint: Gen >V Sd
Group
Gener Protect
Range [units]
Gen <V BOC 200 [%]
Related
applications
All
Description
Threshold for generator overvoltage alarm, relative to the nominal voltage
(setpoint Nominal Volts).
Setpoint: Gen <V BOC
Group
Gener Protect
Range [units]
0 ... Gen >V Sd [%]
Related
applications
All
Description
Threshold for generator undervoltage alarm, relative to the nominal voltage
(setpoint Nominal Volts).