InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
184
Setpoint: Short Crct BOC
Group
Gener Protect
Range [units]
100 ... 500 [%]
Related
applications
All
Description
Limit for the generator short circuit alarm. The delay of this alarm is
adjustable by the setpoint Short Crct Del.
Setpoint: Short Crct Del
Group
Gener Protect
Range [units]
0 ... 10.00 [s]
Related
applications
All
Description
Delay for the generator short circuit alarm. The limit for this alarm is
adjustable by the setpoint Short Crct BOC.
Setpoint: Amps Unbal BOC
Group
Gener Protect
Range [units]
1 ... 200 [%]
Related
applications
All
Description
Threshold for generator current unbalance alarm, relative to the nominal
current (setpoint Nomin Current).
Igen
Nominal Current
Short Crct Sd
Amps IDMT Del
Maximal Reaction time