184
Setpoint: Short Crct BOC
Group
Gener Protect
Range [units]
100 ... 500 [%]
Related
applications
All
Description
Limit for the generator short circuit alarm. The delay of this alarm is
adjustable by the setpoint Short Crct Del.
Setpoint: Short Crct Del
Group
Gener Protect
Range [units]
0 ... 10.00 [s]
Related
applications
All
Description
Delay for the generator short circuit alarm. The limit for this alarm is
adjustable by the setpoint Short Crct BOC.
Setpoint: Amps Unbal BOC
Group
Gener Protect
Range [units]
1 ... 200 [%]
Related
applications
All
Description
Threshold for generator current unbalance alarm, relative to the nominal
current (setpoint Nomin Current).
Igen
Nominal Current
Short Crct Sd
Amps IDMT Del
Maximal Reaction time
Reaction time