InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
263
Binary output: AL Reverse Pwr
Related
applications
All
Description
This output is active when the reverse power alarm is present in the
alarmlist.
Binary output: AL Start Fail
Related
applications
All
Description
This output is active when the start fail alarm is present in the alarmlist.
Binary output: AL Stop Fail
Related
applications
All
Description
This output is active when the stop fail alarm is present in the alarmlist.
Binary output: AL Sync Fail
Related
applications
All
Description
This output is active when the Sync Timeout or RevSyncTimeout is present
in the alarmlist.
Binary output: AL Batt Volt
Related
applications
All
Description
This output is active when the Battery voltage or Battery flat is present in the
alarmlist.
Binary output: AL Earth Fault
Related
applications
All
Description
This output is active when Earth Fault Current alarm is present in alarm list
(extension module IC-NT CT-BIO7 is needed).
Binary output: BI1 Status
Related
applications
All
Description
This output gives information about the status of binary input 1 of the
controller.
If the related binary input is configured as an alarm input, the output
is closed when the assigned alarm is present in the alarmlist.
If the related binary input is configured as functional, the output
copies directly the status of the input.