While the engine shall be stopped
This alarm occurs if the gen-set shall be stopped, but some symptom indicates that it is
not stopped. The period when the gen-set shall be stopped begins after the fuel has
been switched off and time delay Stop time has elapsed and lasts for the entire time the
fuel resp. starter motor are off.
ENGINE STOP ENGINE START
Stop time Stop fail alarm is evaluated here
STARTER
FUEL SOLENOID
See the chapter Cool down and stop to learn more about symptoms that are taken into
account for the evaluation of stopped engine.
NOTE:
The gen-set cannot be started until this alarm is inactive and reset.
Alarm: RPM measurement failure
The alarm is issued if the engine speed has not exceeded the Starting RPM
within the MaxCrank Time, although some of additional running engine
indication sources indicate that the engine has started.