Alarm: Stop fail
Alarm type
Shutdown
Alarmlist
message
Stop fail
Alarm
evaluated
While the engine shall be stopped
Related
applications
All
Description
This alarm occurs if the gen-set shall be stopped, but some symptom indicates that it is
not stopped. The period when the gen-set shall be stopped begins after the fuel has
been switched off and time delay Stop time has elapsed and lasts for the entire time the
fuel resp. starter motor are off.
ENGINE STOP ENGINE START
Stop time Stop fail alarm is evaluated here
STARTER
FUEL SOLENOID
See the chapter Cool down and stop to learn more about symptoms that are taken into
account for the evaluation of stopped engine.
NOTE:
The gen-set cannot be started until this alarm is inactive and reset.
Alarm: RPM measurement failure
Alarm type
Warning
Alarmlist
message
Sd RPMMeasFail
Alarm evaluated
During cranking
Related
applications
All
Description
The alarm is issued if the engine speed has not exceeded the Starting RPM
within the MaxCrank Time, although some of additional running engine
indication sources indicate that the engine has started.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals