InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
5
4
3
2
1
AVRI
AO GND
ST4
IG-
AVRi
TRANS
AVRi trim to minimum counter
clockwise
Volt/PF ctrl:
AVR Bias = 50%
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
1
2
AVRI
AO GND
IG-
AVRi
TRANS
AVRi output is connected instead of external resistor for voltage adjusting.
AVRi trim to approx. 60 %
clockwise.
Volt/PF ctrl:
AVR Bias = 60-70%
Voltage range (-6 V; 6 V)
HINT:
Before you connect IG-AVRi you should connect the jumper on AVR between pin 1 and 2 to run the voltage
regulator without external control and set the voltage by the voltage trim on SX460 to roughly 227 V (in the
event that the nominal voltage of the system is 230 V).
STAMFORD SX 440, AS440, MX 321, SX 421
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
A1
A2
AVRI
AO GND
IG-
AVRi
TRANS
PFC3 module is not required.
AVRi trim to minimum counter
clockwise.
Volt/PF ctrl:
AVR Bias = 50%
18VAC
From
generator
OUT2
OCOM
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
AO GND
AVRI
IG-
AVRi
TRANS
AVRi output is connected instead of external resistor for voltage adjusting.
Volt/PF ctrl:
AVR Bias = 30%