STAMFORD MX 341
18VAC
From
generator
OUT1
OCOM
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
AO GND
AVRI
A1
A2
IG-
AVRi
TRANS
AVRi trim to minimum counter
clockwise.
Volt/PF ctrl:
AVR Bias = 50%
HINT:
Disconnect the droop CT (terminal S1 & S2) and short the droop CT leads.
Short the terminal S1,S2 on the AVR
AVK Newage
AVK Newage Cosimat N+
18VAC
From
generator
OUT1
OCOM
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
AO GND
AVRI
t
S
2
1
5R5
250R
IG-
AVRi
TRANS
Volt/PF ctrl:
AVR Bias = 25%
AVK Newage MA330, 327, 321, 341
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
2
1
A1
A2
AVRI
AO GND
IG-
AVRi
TRANS
AVRi trim to minimum counter
clockwise
Volt/PF ctrl:
AVR Bias = 50%
Caterpillar
Caterpillar CDVR
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
12-3
12-6
AVRI
AO GND
IG-
AVRi
TRANS
AVRi trim to 50%
Volt/PF ctrl:
AVR Bias = 50%