EasyManua.ls Logo

DAB MCE-55/P - Page 382

DAB MCE-55/P
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NEDERLANDS
378
Tabel 30: fabrieksinstellingen
Fabrieksinstellingen
Identificatiecode Beschrijving Waarde
LA Taal NL
SP Setpoint druk [bar] 3,0
P1 Setpoint P1 [bar] 2,0
P2 Setpoint P2 [bar] 2,5
P3 Setpoint P3 [bar] 3,5
P4 Setpoint P4 [bar] 4,0
FP Testfrequentie in handbediende modus 40,0
RC Nominale stroom van de elektropomp [A] 0,0
RT Draairichting 0 (UVW)
FN Nominale frequentie [Hz] 50,0
OD Installatietype 1 (Star)
RP Drukvermindering voor herstart [bar] 0,5
AD Adres 0 (Auto)
PR Druksensor 1 (501 R 25 bar)
MS Matenstelsel 0 (Internationaal)
FI Debietsensor 1 (Flow X3 F3.00)
FD Diameter leiding [inch] 2
FK K-factor [puls/l] 24,40
FZ Frequentie nuldebiet [Hz] 0
FT Minimumdebiet voor uitschakeling [ l/min] 5
SO Factor bedrijf zonder vloeistof 22
MP Minimumdrempel druk [bar] 0,0
TB Tijd van blokkering wegens ontbreken water [s] 10
T1 Uitschakelvertraging [s] 2
T2 Uitschakelvertraging [s] 10
GP Coëfficiënt van proportionele stijging 0,6
GI Coëfficiënt van integrale stijging 1,2
FS Maximale rotatiefrequentie [Hz] 50,0
FL Minimale rotatiefrequentie [Hz] 0,0
NA Actieve inverters N
NC Gelijktijdig werkende inverters NA
IC Configuratie van de reserve 1 (Auto)
ET Uitwisselingstijd [h] 2
CF Draaggolffrequentie [kHz] 5
AC Versnelling 3
AE Antiblokkeerfunctie 1 (Geactiveerd)
I1 Functie I1 1 (Vlotter)
I2 Functie I2 3 (P Aux)
I3 Functie I3 5 (Disable)
I4 Functie I4 10 (lage druk)
O1 Functie uitgang 1 2
O2 Functie uitgang 2 2