Dell PowerEdge XE9680 - Intrusion switch; Removing the intrusion switch module

Dell PowerEdge XE9680
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Align the power interposer board with the connector on the system board.
3. Pull the plunger and slide the power interposer board toward front of the chassis until the plunger clicks into place.
Figure 99. Installing the power interposer board
4. Connect the cables within the busbar to the connectors on the system board.
Next steps
1. Replace the PSU cage.
2. Observe and connect the cables to the connectors on the power distribution board.
3. Replace the air shroud
4. Replace the cooling fan cage assembly.
5. Replace the front top cover.
6. Follow the procedure listed in After working inside your system.
Intrusion switch
This is a service technician replaceable part only.
Removing the intrusion switch module
Prerequisites
1. Follow the safety guidelines listed in the Safety instructions.
2. Follow the procedure listed in the Before working inside your system.
3. Remove the cooling fan cage assembly.
4. Remove the air shroud.
5. Observe and disconnect the cables from the connectors on the power distribution board.
6. Remove the PSU cage.
NOTE:
Ensure that you note the routing of the cable as you remove it from the system board. Route the cable properly
when you replace it to prevent the cable from being pinched or crimped.
Installing and removing system components 131