NOTE: PowerEdge XE9680 system supports 5+1 PSU redundancy which means only one PSU is redundant. A/B Grid
Redundant setting in iDRAC is not supported.
NOTE: PowerEdge XE9680 system also supports 3+3 PSU redundancy. When two or more PSUs are down, this fault
tolerant redundant mode triggers GPU power brake and GPU clocks are throttled to one-fourth and GPU performance will
drop to around one-fifth.
NOTE: This system is also designed to connect to the IT power systems with a phase-to-phase voltage not exceeding 240
V.
NOTE: Heat dissipation is calculated using the PSU wattage rating.
NOTE: Do not mix PSUs from different vendors within a single system configuration to ensure optimal performance and
reliability.
Figure 23. PSU C22 Input Socket
Figure 24. PSU power cord
Table 12.
PSU power cord
Form factor Output Power cord
Redundant 86 mm 2800 W AC C22/C21
Redundant 86 mm 3200 W AC APP 2006G1
NOTE: 2800W 54V PSU has a C22 input socket that requires C21 to C20 jumper cord to connect it to PDU in the rack.
Traditional high amperage power cords C20/C19 cannot be inserted into the PSU.
NOTE: When selecting or upgrading the system configuration, to ensure optimum power utilization, verify the system
power consumption with the Enterprise Infrastructure Planning Tool available at calc.