95-8533
6-5
18.2
SUPERVISED OUTPUT RATING-SIGNAL-
ING CIRCUIT
MAXIMUM OUTPUT CURRENT
(Per Channel)—
2 amperes at 30 Vdc maximum.
Automatic short circuit protection provided.
Instantaneous short circuit current < 15
amperes.
SUPERVISORY CURRENT (Per Channel)—
Reverse current monitored at 1.5 mA, ± 0.5
mA.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging an alarm command message.
EOL RESISTORS—
10 K ohms ±2 K ohms. Each circuit must have
an EOL resistor.
SIGNALING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– 60 beats per minute
– 120 beats per minute
– Temporal Pattern.
Note: All eight channels are synchronized
when programmed as a signaling output.
SUPERVISED OUTPUT RATING-
RELEASING CIRCUIT
MAXIMUM OUTPUT CURRENT
(Per Channel)—
2 amperes at 30 Vdc maximum.
Automatic short circuit protection provided.
Instantaneous short circuit current < 15
amperes.
SUPERVISORY CURRENT (Per Channel)—
Monitored at 1.3 mA ±0.2 mA.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging an alarm command message.
RELEASING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– Timed.
For Class A wiring on outputs, configure
adjacent channels for Class A wiring and
connect both channels to single output
device(s).
NOTE
EDIO SIL has the capability of monitoring
solenoid circuits for shorts. The minimum
solenoid inductance for correct operation
is 100 mH. See Table 3-10 for a list of
recommended solenoids.
EQ3700 DISCRETE IO
(DCIO) MODULE
POWER REQUIREMENTS—
3 watts nominal, 11 watts maximum.
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
NOTE: Pre-action and deluge applications
further limit the lower operatring voltage range,
refer to DCIO installation instructions in section
3.
OUTPUT VOLTAGE—
(Input voltage – 0.5 Vdc) @ 2 amperes.
OUTPUT CURRENT—
10.0 amperes maximum total current, 2.0
amperes maximum per channel.
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
Refer to Figure 6-3.
SHIPPING WEIGHT—
1 pound (0.45 kilograms).
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Refer to Appendix A for FM Approval details.