15.4 iMeter Replacement
1
Turn off power to the dispenser.
2
Trip sheer valve.
3
Place a container under the meter to catch fuel spill, and place absorbent pads down around
dispenser.
4
Loosen the two screws on the WIP and remove WIP from meter and set aside. Fig 15.27.
Figure 15.27: Remove WIP
5
Loosen 10 mm screws on meter valve retaining plate and rotate plate. Fig 15.28.
Figure 15.28: Valve retaining plate
260 WM048523 Rev 08 01/2019
15 Helix 6000 DEF, Extra Narrow Model Dispensers - IEC