15
Reinstall spring washer and coil onto valve, and then reinstall the name plate onto coil.
16
Ensure that magnet washer on the conduit is pushed up against the bottom of vapor barrier.
17
Reset the emergency shear valve.
18
Turn power on to dispenser and submersible pump, test operation and check for leaks.
18.2 Check Valve Replacement
Reference photos (A) through (D) during this procedure.
A check valve is located in the meter outlet (behind the proportional valve) on side A and on side
B. The check valve, with the proportional valve removed, is shown in (A) below.
Adhere to the two Warnings at the beginning of this section before attempting to remove
the check valve.
Reference photos (A) through (D) during this procedure.
A check valve is located in the meter outlet (behind the proportional valve on side A and on side
B. The check valve, with the proportional valve removed, is shown in (A) below.
A
Screw (2) securing retaining ring
NOTE: These screws are shorter than the
proportional valve bracket screws.
Check valve, spring, and o-ring
Check valve is located in the meter outlet
(behind the proportional valve)
Check valve and o-ring are the same as the
Xflo, but the spring is different
WIP
(green case)
1
Perform the steps 1-10 in the previous section for removing proportional valve.
2
Using a 10 mm open end wrench, remove the (2) hex head screws (A above) from check
valve retaining ring. See Note above.
3
Pry out the check valve retainer and then remove the O-ring (B) and (C).
314 WM048523 Rev 08 01/2019