C
B
Use flat blade
screwdriver
4
Remove the spring and check valve from the meter outlet. (D).
D
5
Install new check valve and reinstall spring. (Valve and spring P/N WM029220-0003)
6
Install new o-ring and lubricate o-ring with petroleum jelly. (O-ring P/N WM022490)
7
Reinstall retaining ring and secure using the (2) screws. Be sure to use the screws that were
removed in step 2. These screws are shorter than the proportional valve bracket screws.
8
Reinstall proportional valve and coil
9
Reset the emergency shear valve.
10
Turn power on to dispenser and submersible pump, test operation and check for leaks.
WM048523 Rev 08 01/2019 315