16.5 Degassing Unit Filter Replacement
1
Close in ground inlet valve.
2
Relieve pressure per step 3 in section 16.1.
3
Turn off power to the dispenser.
4
Loosen the small screw on the filter cap, then loosen cap and remove. Fig 16.38.
Figure 16.38: Filter cap
5
Remove filter. Fig 16.39.
Figure 16.39: Filter
6
Clean or replace filter as necessary.
7
Open all valves.
8
Turn on power.
9
Verify there are no leaks.
302 WM048523 Rev 08 01/2019