Configuration
October 2018
Configuration
How to change the Modbus address of the Rosemount 2460 System Hub
a. In the 2460 Communication window click the Change Address on Device button to open the
Change Address window:
b. Enter the Device ID and the new Modbus address. For the Rosemount 2460 System Hub it is
recommended to use address 201 and up.
When changing the device address, the Device ID is used as a unique identifier of the device. The
Device ID can be found on a label mounted on the device.
Tip! If there is no other device connected that uses the same address as the current device, you
can find the Device ID by typing the current address into the Address field in the Rosemount 2460
System Hub Communication window and clicking the Verify Communication button.
c. Click the OK button to confirm the settings and close the Change Address window.
d. In the Rosemount 2460 System Hub Communication window click the Verify Communication
button to check if communication is established between the TankMaster work station and the
Rosemount 2460 System Hub. The Device ID will appear when TankMaster finds the system hub.